78 Installation checklist
Make sure that ...
There is an adequately sized protective earth (ground) conductor between the drive
and the switchboard.
There is an adequately sized protective earth (ground) conductor between the motor
and the drive.
All protective earth (ground) conductors are connected to the correct terminals and the
terminals are tightened (pull the conductors to check).
The supply voltage matches the nominal input voltage of the drive. Read the type
designation label.
The input power cable is connected to the correct terminals, the phase order is right,
and the terminals are tightened. (Pull the conductors to check.)
Appropriate supply fuses and disconnector are installed.
The motor cable is connected to the correct terminals, the phase order is right, and the
terminals are tightened. (Pull the conductors to check.)
The brake resistor cable (if present) is connected to the correct terminals, and the
terminals are tightened. (Pull the conductors to check.)
The motor cable (and brake resistor cable, if present) is routed away from other
cables.
The control cables (if any) are connected.
If a drive bypass connection is used: The direct-on-line contactor of the motor and the
drive output contactor are mechanically or electrically interlocked (cannot be closed
simultaneously).
There are no tools, foreign objects or dust inside the drive. There is no dust near the
air inlet of the drive.
The drive cover is in place.
The motor and the driven equipment are ready for start-up.