Alternative Power Cable Types; Recommended Power Cable Types; Power Cable Types For Limited Use - ABB ACS880-07 Hardware Manual

Industrial drives (45 to 630 kw, 50 to 700 hp)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

74 Guidelines for planning the electrical installation
Drive type
ACS880-07-0271A-7
ACS880-07-0330A-7
ACS880-07-0370A-7
ACS880-07-0425A-7
ACS880-07-0470A-7
ACS880-07-0522A-7
ACS880-07-0590A-7
ACS880-07-0650A-7
1. The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1
and IEC 60364-5-52/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.
2. The cable sizing is based on NEC Table 310-16 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth
(directly buried). For other conditions, size the cables according to local safety regulations, appropriate input
voltage and the load current of the drive.

Alternative power cable types

The recommended and not allowed power cable types to be used with the drive are
presented below.

Recommended power cable types

PE
PE
PE

Power cable types for limited use

PE
Frame
IEC
size
Cu cable type
2
mm
R9
3×240
R10
2 × (3×120)
R10
2 × (3×120)
R11
3 × (3×95)
R11
3 × (3×95)
R11
3 × (3×120)
R11
3 × (3×150)
R11
3 × (3×150)
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. The shield must meet the requirements of IEC 61439-1,
see page 72. Check with local / state / country electrical codes for allowance.
Symmetrical shielded cable with three phase conductors and a concentric PE
conductor as shield. A separate PE conductor is required if the shield does not
meet the requirements of IEC 61439-1, see page 72.
Symmetrical shielded cable with three phase conductors and symmetrically
constructed PE conductor, and a shield. The PE conductor must meet the
requirements of IEC 61439-1.
A four-conductor system (three phase conductors and a protective conductor on
a cable tray) is not allowed for motor cabling (allowed for input cabling).
1)
Al cable type
2
mm
2 × (3×120)
3 × (3×120)
3 × (3×120)
3 × (3×120)
3 × (3×150)
3 × (3×185)
2×500 MCM or 3×250 MCM
3 × (3×185)
2×600 MCM or 3×300 MCM
3 × (3×240)
2×700 MCM or 3×350 MCM
2)
US
Cu cable type
AWG/kcmil per phase
400 MCM
2×250 MCM or 3×2/0
2×300 MCM or 3×3/0
2×350 MCM or 3×4/0
2×400 MCM or 3×4/0