the protective earthing conductor shall be determined in a manner which produces a
conductance equivalent to that which results from the application of this table:
Cross-sectional area of the phase
conductors S (mm
S < 16
16 < S < 35
35 < S
Refer to the IEC/EN 61800-5-1 requirement on grounding on page 17.

Typical power cable sizes

These are the typical cross-sectional area of the power cables at the nominal drive
current.
Drive type
1-phase U
= 200...240 V
N
ACS380-04xx-02A4-1
ACS380-04xx-03A7-1
ACS380-04xx-04A8-1
ACS380-04xx-06A9-1
ACS380-04xx-07A8-1
ACS380-04xx-09A8-1
ACS380-04xx-12A2-1
3-phase U
= 200...240 V
N
ACS380-04xx-02A4-2
ACS380-04xx-03A7-2
ACS380-04xx-04A8-2
ACS380-04xx-06A9-2
ACS380-04xx-07A8-2
ACS380-04xx-09A8-2
ACS380-04xx-12A2-2
ACS380-04xx-17A5-2
ACS380-04xx-25A0-2
ACS380-04xx-032A-2
ACS380-04xx-048A-2
ACS380-04xx-055A-2
3-phase U
= 380...480 V
N
ACS380-04xx-01A8-4
Minimum cross-sectional area of the
2
)
corresponding protective conductor S
Frame
mm
R0
3×1.5 + 1.5
R0
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R2
3×2.5 + 2.5
R2
3×2.5 + 2.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×1.5 + 1.5
R1
3×2.5 + 2.5
R2
3×2.5 + 2.5
R3
R3
R4
3×10 + 10
R4
3×25 + 16
R4
3×25 + 16
R0
3×1.5 + 1.5
Planning the electrical installation 49
2
(mm
)
S
16
S/2
2
(1
(Cu)
3×6 + 6
3×6 + 6
p
AWG
16
16
16
16
16
14
14
16
16
16
16
16
14
14
14
10
8
4
4
16