Control Connection Data - ABB ACS380 Hardware Manual

Hide thumbs Also See for ACS380:
Table of Contents

Advertisement

Control connection data

Analog inputs
(AI1, AI2)
Analog output
(AO)
Auxiliary voltage
input/output (+24V)
Digital inputs
(DI1...DI4)
Programmable
digital I/O
(DIO1, DIO2)
Relay output
(RA, RB, RC)
Frequency input
(FI)
Frequency output
(FO)
STO interface
(SGND, S+, S1, S2)
Voltage signal,
0...10 V DC (10% overrange, 11 V DC max.)
single-ended
R
in
Current signal,
0...20 mA (10% overrange, 22 mA max.)
single-ended
R
in
Inaccuracy
≤ 1.0%, of full scale
Overvoltage
up to 30 V DC
protection
Potentionmeter
10 V DC ±1%, max. load current 10 mA
reference value
Current output
0...20 mA (10% overrange, 22 mA max.) into 500 ohm
mode
load
Voltage output
0...10 V DC (10% overrange, 11 V DC max.) into
mode
200 kohm minimum load (resistive)
Inaccuracy
≤ 1.0%, of full scale
As output
+24 V DC ±10%, max. 200 mA
As input
+24 V DC ±10%, max. 1000 mA (incl internal fan load)
Voltage
12...24 V DC (int. or ext. supply) Max. 30 V DC.
Type
PNP and NPN
Input impedance R
in
As inputs
Voltage
Type
Input impedance
As outputs
Type
Max. switching voltage 30 V DC
Max. switching current
Frequency
Resolution
Type
1 From C (NO + NC)
Max. switching
250 V AC / 30 V DC
voltage
Max. switching
2 A
current
10 Hz...16 kHz
DI3 and DI4 can be used as digital or frequency inputs.
DIO1 and DIO2 can be used as digital or frequency outputs.
Refer to
Safe torque off function
= 221.6 kohm
= 137 ohm
= 2 kohm
on page 139.
Technical data 109
12...24 V DC with internal or
external supply. Max.
30 V DC.
PNP and NPN
R
= 2 kohm
in
Transistor output PNP
70 mA / 30 V DC,
short-circuit protected
10 Hz...16 kHz
1 Hz

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents