ABB ACS380 Hardware Manual page 50

Hide thumbs Also See for ACS380:
Table of Contents

Advertisement

50 Planning the electrical installation
Drive type
ACS380-04xx-02A6-4
ACS380-04xx-03A3-4
ACS380-04xx-04A0-4
ACS380-04xx-05A6-4
ACS380-04xx-07A2-4
ACS380-04xx-09A4-4
ACS380-04xx-12A6-4
ACS380-04xx-17A0-4
ACS380-04xx-25A0-4
ACS380-04xx-032A-4
ACS380-04xx-038A-4
ACS380-04xx-045A-4
ACS380-04xx-050A-4
1) This is the size of typical power cable (symmetrical, shielded, three-phase copper cable). Note that for the
input power connection, you typically must have two separate PE conductors, i.e., the shield alone is not
enough. Refer to
Grounding
Refer also to
Terminal data for the power cables
Frame
R1
R1
R1
R1
R1
R1
R2
R3
R3
R4
R4
R4
R4
on page 17.
2
(1
mm
(Cu)
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×1.5 + 1.5
3×2.5 + 2.5
3×2.5 + 2.5
3×6 + 6
3×6 + 6
3×10 + 10
3×16 + 16
3×25 + 16
3×25 + 16
on page 103.
AWG
16
16
16
16
16
14
14
10
10
8
6
4
4

Hide quick links: