98 Technical data
1) Maximum allowed rated conditional short-circuit current (IEC 61800-5-1) of the electrical power network.
Self-protected combination manual controller – Type E
USA (UL) environment
You can use the ABB Type E manual motor protectors MS132 & S1-M3-25, MS165-
xx and MS5100-100 as an alternate to the recommended fuses as a means of branch
circuit protection. This is in accordance with the National Electrical Code (NEC).
When the correct ABB Type E manual motor protector is selected from the table and
used for branch circuit protection, the drive is suitable for use in a circuit capable of
delivering no more than 65 kA RMS symmetrical amperes at the drive's maximum
rated voltage. See the following table for the appropriate ratings. See the MMP rating
table for the minimum enclosure volume of IP20 open type ACS380 mounted in an
enclosure.
Type code
1-phase U
= 200...240 V
N
(200, 208, 220, 230, 240 V)
ACS380-04xx-02A4-1
ACS380-04xx-03A7-1
ACS380-04xx-04A8-1
ACS380-04xx-06A9-1
ACS380-04xx-07A8-1
ACS380-04xx-09A8-1
ACS380-04xx-12A2-1
3-phase U
= 380...480 V (380, 400, 415, 440, 460, 480 V)
N
ACS380-04xx-01A8-4
ACS380-04xx-02A6-4
ACS380-04xx-03A3-4
ACS380-04xx-04A0-4
ACS380-04xx-05A6-4
ACS380-04xx-07A2-4
ACS380-04xx-09A4-4
ACS380-04xx-12A6-4
ACS380-04xx-17A0-4
ACS380-04xx-25A0-4
ACS380-04xx-032A-4
ACS380-04xx-038A-4
ACS380-04xx-045A-4
ACS380-04xx-050A-4
1) All manual motor protectors listed are Type E self-protected up to 65 kA. See the ABB publication
2CDC131085M0201 – Manual Motor Starters – North American Applications for complete technical data on
the ABB Type E manual motor protectors. In order for these manual motor protectors to be used for branch
circuit protection, they must be UL listed Type E manual motor protectors, otherwise they can be used only as
an At Motor Disconnect. "At Motor Disconnect" is a disconnect just ahead of the motor on the load side of the
panel.
2) Manual motor protectors may require adjusting the trip limit from the factory setting at or above the drive
input Amps to avoid nuisance tripping. If the manual motor protector is set to the maximum current trip level
and nuisance tripping is occurring, select the next size MMP. (MS132-10 is the highest size in the MS132
frame size to meet Type E at 65 kA; the next size up is MS165-16.)
3) Requires the use of the S1-M3-25 line side feeder terminal with the manual motor protector to meet Type E
self-protection class.
Frame
MMP type
R0
MS132-6.3 & S1-M3-25
R0
MS132-10 & S1-M3-25
R1
MS165-16
R1
MS165-16
R1
MS165-20
R2
MS165-25
R2
MS165-32
4) 5)
R0
MS132-4.0 & S1-M3-25
R1
MS132-6.3 & S1-M3-25
R1
MS132-6.3 & S1-M3-25
R1
MS132-10 & S1-M3-25
R1
MS132-10 & S1-M3-25
R1
MS165-16
R1
MS165-16
R2
MS165-20
R3
MS165-32
R3
MS165-42
R4
Contact ABB
R4
Contact ABB
R4
Contact ABB
R4
Contact ABB
Minimum enclosure volume
1) 2)
3
dm
3)
30.2
3)
30.2
30.2
30.2
30.2
30.2
30.2
3)
30.2
3)
30.2
3)
30.2
3)
30.2
3)
30.2
30.2
30.2
30.2
30.2
30.2
5)
cu in
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842
1842

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents