Mechanical installation

Refer to
To install a side option

Electrical installation

WARNING! Obey the instructions in
ignore them, injury or death, or damage to the equipment can occur.

Terminal designations

The relay interface of the BREL module consists of four 1×3-pin terminal blocks.
Use this table for reference when you wire the terminals
Identification
X103
1
COM
2
NC
3
NO
X104
1
COM
2
NC
3
NO
X105
1
COM
2
NC
3
NO
X106
1
COM
2
NC
3
NO

Wiring

2
Use 0.5 to 2.5 mm
signals.
Refer to
Terminal designations
module.

Apply power

1. Turn on the input power to the drive.
2. Continue with
Start-up
on page 76.
Output relays 2-5:
• Max. switching voltage: 250 V AC / 30 V DC
• Max. switching current: 2 A
Galvanically isolated.
2
Inductive loads (such as contactor coils): Protect the relay contacts as
recommended in
3
4
5
(20 to 14 AWG) cable with an appropriate voltage rating for digital
on page
on page 174.
BREL-01 relay output extension module 173
Safety instructions
.
Description
Protecting the contacts of relay outputs
173
and connect control wires to the BREL
on page 13. If you
on page 59.