Byte 2: Program Number, Reference Point Or Eeprom Ram Parameters; Byte 3: Override Factor - Siemens SIMATIC S5 Manual

Ip 266 positioning module
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

IP 266
7.1.3
Byte 2: Program Number, Reference Point or
EEPROM RAM Parameters
The contents of this byte depend on the specified mode.
In modes 5, 8, 9, 10 and 26, byte 2 is used as byte parameter. It is irrelevant in all
other modes.
Mode
Use
5
Reference point:
Bit 0 = 0 : approach
Bit 0 = 1 : set
8
Number of the machining
9
program
10
26
Direction of data transfer:
IP EEPROM IP RAM
Bit 0 = 0 : RAM EEPROM
1 : EEPROM RAM
7.1.4

Byte 3: Override Factor

Byte 3 is the second of the byte parameters, and contains the override factor. A
valid value must be entered in this byte for all modes which allow modification of
the speed via an override factor. The value must be in the range from 1% to 200%,
and should be entered in KF (fixed-point constant) format if possible. The over-
ride factor is transferred in byte 1 to the IP 266 with "TRANSFER".
EWA 4NEB 812 6057-02
Communication Between the CPU and the IP 266
KM FORMAT
7
6
5
4
3
2
1
0
0
0
0
0
0
0
X: variable; bit 1 to 7 irrelevant
0
0
0
0
0
0
0
Example: This bit combination is
used to transfer data from the
IP 266's EEPROM to IP RAM, i.e.
the current RAM contents are
overwritten.
KF FORMAT
0
X
Example:
KF = +7
Program no. 7
1
7-7