Setting The Dnp Points; Using The Dnp Configure Program For A Custom Dnp Point Set; Selecting A Predefined Dnp Point Set; Dnp Point Set For Mj-4A Or Mj-4B - Siemens MJ-4 Series Installation Manual

Communications module, fiber optic and rs-232/485, for mj-4a, mj-xl and mj-x control panels
Table of Contents

Advertisement

8 Setting the DNP points

This section describes how to set the DNP points that will be used on the control panel, You can use the DNP
Configure program to customize your DNP point set or you can use one of the predefined point sets listed in section
8.2.
In order to use a customized point set, an MJ-X
use predefined point sets (except Set 7), an MJ-X
available on the MJ-4 Control.
It is recommended that a Latching Relay command be used for all Binary Outputs (e.g., remote raise/lower, auto
inhibit, etc.).

8.1 Using the DNP Configure program for a custom DNP point set

The DNP Configure program is used to place a custom set of user-defined DNP points on the control panel. You
can obtain this program free-of-charge from your Siemens representative. After installing the program, run it and
follow the steps below to set your DNP points.
1. Connect your computer's com port to the panel's Data Port with a "straight-thru" male-female DB9
cable.
2. If you already have a DNP points profile, open it and go to Step 8. To open an existing points profile, in
the menu bar: click File
3. Click the Class 0 button. Move between the tabs and checkmark the points you want. Click OK.
4. If Class 1, 2, or 3 polls are desired, these can now be set the same way.
5. Click the Send button. Drag and drop the points up and down in the list boxes to change their point
number if desired. The top point in each box is point # 0, the point below that is point # 1, etc. Click
the Cancel button after points are ordered as desired.
6. In the menu bar: click File
7. Click the Setting button.
8. Match the baud rate and parity between the computer and the panel. Choose the COM port your
computer is using. Set Addressing to be Disabled (if MJ-4's "DataPortAddr" setting is OFF). Click OK.
9. Click the Send button.
10. Click the Send button on the bottom of the points list screen.
11. If successful, a window will pop up displaying "Send Communication Status: OK..." Click OK.
12. DNP Configure can be closed or you can use the same point set to configure other panels.

8.2 Selecting a predefined DNP point set

8.2.1 DNP point set for MJ-4A or MJ-4B

When the MJ-4 Communications Module with firmware version 3.10 (initial release) or higher is interfaced with a
MJ-4A or MJ-4B, you will be able to choose from a number of DNP point sets, including Set 7. Sets 8 through 15
are not defined at this time.

8.2.2 DNP Point set for other Control Panels

The MJ-4 Communications Module may be used with the MJ-X
available may be limited. The operation and functionality of the MJ-4 Communications Module is similar to older
versions of the Communications Module though either the Fiber Optic or the RS-232/485 interfaces may be used at
a time. If the control panel is an MJ-X
L
must have version 3.06 and the MJ-X must have 2.52. In order to
L
must have version 3.07 and a MJ-X must have 2.53. Set 7 is only
Open and select your file. Otherwise go to Step 3 to create a points profile.
Save and save your file as XXXX.dnp
L
with firmware version 3.07 or higher (or an MJ-X with version 2.53 or
MJ-4 Communications Module
L
or MJ-X control panels, but the DNP sets
21