STEP 5 Programming
Every "Command FB" includes the following code-evaluation routine:
Input set
yes
AND auxiliary flag
not set?
no
Edge flag = 0
yes
Input set?
no
Auxiliary flag = 0
This routine works with auxiliary flags and edge flags, and ensures that a
command is entered in the output byte only once in the first cycle that follows
setting of the input. Edge flag 4.1 is used for this purpose.
0th cycle
Switch/key is actuated
1st cycle
Input appears in the PII as being set
Auxiliary flag
Edge flag
2nd to nth cycle
Input remains set
Auxiliary flag
Edge flag
9-26
Setting auxiliary flags and edge flags
Edge flags
Edge flag = 1
Auxiliary flags
Auxiliary flag = 1
= 1
= 1
= 1
= 0
IP 266
A
I 3.1
AN
F 4.0
=
F 4.1
A
I 3.1
=
F 4.0
Frame
is entered in output byte
is not entered in output byte