Troubleshooting
Troubleshooting
Error Code
F0C Wrong module number
When <F1> (Start) is pressed in the PRESETS form, the COM 266 software
executes a module identification test. When a set of machine data is
entered on the IP 266, the specified module number is compared with the
module number in the machine data. The machine data must contain the
same number as the one entered.
F0D
Zero offset too large
Every zero offset may assume values in the range +/-32767.999 mm.
Among other things, a zero offset changes the coordinates of the software
limit switches. Each offset value must be such that the coordinates of the
software limit switches still lie in the range from +/-32767.999 mm
(+/-32767.999 inches, +/-32767.999 degrees) after being shifted.
F0E
Wrong tool offset
A tool offset is restricted to +/-32767.999. The coordinate of the software
end limit switch plus zero offset and the coordinate of the software start
limit switch plus zero offset must lie in the range +/-32767.999 mm
(+/-32767.999 inches, +/-32767.999 degrees). Remember that the zero
offset is a signed value. In the case of a rotary axis, the tool offset must also
lie within the traversing range.
F0F
Position tolerance out of range
The tolerance range for zero-speed monitoring extends from 0.001 to
64.999 mm, and must also be less than the maximum following error.
F10
Inadmissible input
10-6
IP 266
Cross-
Reference
Section 5.1.1
Section 5.1.7
Section 5.1.7
Section 5.1.6