Siemens SIMATIC S5 Manual page 340

Ip 266 positioning module
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

Troubleshooting
Error Code
Recovery Procedures
FA1
Watch-Dog
FA2
Watch-Dog
FA3
Error at block start
FA4
Sub-program DB-No too large
The DB number must lie in the range from 1 to 255.
FA5
G-function prohibited
FA6
Loop only as outer loop
FA7
Nesting depth exceeded
FA8
Wrong X-function
FA9
Wrong F-function
FAA
Stroke too long (traversing path too long)
FAB
Machining speed too high (traversing speed too high)
FAC
Error at block end
FAD
End of program precedes end of loop
FAE
Block not permitted after flying change
FB0
Machining program erroneous (error in traversing program)
FB1
Machining (traversing) program already exists! Change Prog-No?
10-14
IP 266
Cross-
Reference
Section 5.3.18
Section 5.3.18
Section 5.5.4
Section 5.4.2
Section 5.4.2
Section 5.4.2
Section 5.4.2
Section 5.4.2
Section 5.4
EWA 4NEB 812 6057-02