" E2-03 No Load Current

Setting Range:
Model Dependent (see Appendix B)
Factory Default: Model Dependent
Set E2-03 to the motor no-load current at rated voltage and rated frequency. Consult the motor manufacturer for the proper
value if the no load current is not stated on the motor nameplate.
!

F6 Com OPT Setup (applies only to the LonWorks option)

" F6-01 Operation Selection After Communication Error

Setting
0
Ramp to Stop
1
Coast to Stop (factory default)
2
Fast-Stop
3
Alarm Only
If a serial communication option board is attached to the Drive at the 2CN connector, the Drive will automatically monitor the
card for any type of communication errors. F6-01 is applicable no matter whether a run command or speed command is coming
via the option board, digital operator, or terminal input. The setting of F6-01 determines whether the communication error is
seen as a fault or an alarm. If F6-01= "3: Alarm Only", then the fault output is not energized upon a communication error. All
other settings of F6-01 cause the fault output to energize. The setting of F6-01 does not apply to any of the embedded
communication protocols used at the RS-485/422 terminals on the removable terminal board. (See parameters H5-0X).

" F6-02 Option PCB External Fault Detection Selection

Setting
0
Always Detected (factory default)
1
Detected only during operation
" F6-03 Option PCB External Fault Stopping Method
Setting
0
Ramp to Stop
1
Coast to Stop (factory default)
2
Fast-Stop
3
Alarm Only
If an external fault is received from the L
determine the Drive operation in reaction to the fault signal. Parameter F6-02 will determine if the external fault is always
recognized (F6-02= "0: Always Detected") or only recognized when the Run command is active (F6-02= "1: Detected only
during operation").
Once the fault is recognized, parameter F6-03 will determine the operation of the Drive. If parameter F6-03 is set to anything
other then "3", the Drive will fault and a stopping sequence is begun. If F6-03= "3: Alarm Only", then the external fault is
treated like an alarm. Operation will continue and an EF0 fault will flash on the digital operator.
Description
Description
Description
ORKS ®
W
or other communication option card, the settings of F6-02 and F6-03 will
ON
Programming 5 - 32