E2 Motor Setup; E2-01 Motor Rated Current; Custom V/F Pattern Programming Curve - YASKAWA P7 User Manual

Table of Contents

Advertisement

To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be
sure that the following condition is true:
E1-09 ≤ E1-07 ≤ E1-06 ≤ E1-11 ≤ E1-04
Max Voltage E1-05
Mid Voltage B E1-12
Base Voltage E1-13
Mid Voltage A E1-08
Min Voltage E1-10
Increasing the voltage in the V/f pattern increases the available motor torque. However, when setting a custom V/f pattern,
increase the voltage gradually while monitoring the motor current, to prevent:
Drive faults as a result of motor over-excitation
Motor overheating or excessive vibration
!

E2 Motor Setup

" E2-01 Motor Rated Current

Setting Range:
Model Dependent (see Appendix B)
Factory Default: Model Dependent
The Motor Rated Current parameter (E2-01) is necessary information for the Drive motor protection function. The motor
overload protection parameter L1-01 is enabled by default. In addition, motor rated current is used by the torque compensation
function to insure optimum torque production. Set E2-01 to the full load amps (FLA) value stamped on the motor's
nameplate. During Auto-tuning, it is required for the operator to enter the motor rated current in parameter T1-04 on the
Auto-Tuning menu. If the Auto-tuning operation completes successfully, the value entered into T1-04 will be also written into
E2-01.
For applications employing a Drive that is oversized for the motor, E2-01 may be set as low as 10% of the Drive output current
rating. The AMP value in E2-01, however, must always be greater than the "No Load Current" value in parameter E2-03 or an
OPE02 error will be displayed.
E1-09
E1-07 E1-06
Min
Mid
Base
Freq
Freq A
Freq
Freq
A
Fig. 22 Custom V/f Pattern Programming Curve
Programming 5 - 31
Frequency
E1-04
E1-11
Mid
Max
Freq B
Freq

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents