Torque Comp; Carrier Freq; Preset Reference (Speeds) - YASKAWA P7 User Manual

Table of Contents

Advertisement

Parameter
Parameter Name
No.
Digital Operator Display
C4-01
Torque Compensation Gain
!
Torq Comp Gain
Torque Compensation
Primary Delay Time
C4-02
Torq Comp Time
1: Normal Duty 1
C6-01
2: Normal Duty 2
Carrier Frequency Selection
C6-02
CarrierFreq Sel
Carrier Frequency Upper
C6-03
Limit
CarrierFreq Max
Carrier Frequency Lower
C6-04
Limit
CarrierFreq Min
Carrier Frequency Propor-
C6-05
tional Gain
CarrierFreq Gain
d1-01
Frequency Reference 1
!
Reference 1
d1-02
Frequency Reference 2
!
Reference 2
d1-03
Frequency Reference 3
!
Reference 3
d1-04
Frequency Reference 4
!
Reference 4
d1-17
Jog Frequency Reference
!
Jog Reference
!Denotes that parameter can be changed when the drive is running.
Table 1: Parameter List (Continued)
Description

Torque Comp

This parameter helps to produce better starting torque. It
determines the amount of torque or voltage boost based upon
motor current and motor resistance.
This parameter adjusts a filter on the output of the torque
compensation function. Increase to add torque stability, decrease
to improve torque response.

Carrier Freq

Reduced Current Rating
Standard Current Rating
Carrier frequency sets the number of pulses per second of the out-
put voltage waveform.
0: Low Noise (Carrier frequency is randomly moduled for lower
audible noise)
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program (Determined by the settings of C6-03 thru C6-05)
Maximum carrier frequency allowed when C6-02 = F.
Minimum carrier frequency allowed when C6-02 = F.
Sets the relationship of output frequency to carrier frequency when
C6-02 = F.

Preset Reference (Speeds)

Digital preset speed command 1. Used when b1-01 = 0. Setting
units are affected by o1-03.
Digital preset speed command 2. Selected via multi-function input
terminals. Setting units are affected by o1-03.
Digital preset speed command 3. Selected via multi-function input
terminals. Setting units are affected by o1-03.
Digital preset speed command 4. Selected via multi-function input
terminals. Setting units are affected by o1-03.
Speed command used when a jog is selected via multi-function
input terminals. Setting units are affected by o1-03.
Parameters A - 8
Setting
Factory
Menu
Range
Setting
Location
0.00 to 2.50
1.00
Programming
0 to 10000
200ms
Programming
1 or 2
2
Programming
kVA
0 to F
Programming
Dependent
kVA
kVA
Programming
Dependent
Dependent
kVA
kVA
Programming
Dependent
Dependent
0 to 99
0
Programming
0.00Hz
Programming
0.00Hz
Programming
0.00 to
E1-04
Value
0.00Hz
Programming
0.00Hz
Programming
0.00 to
E1-04
6.00Hz
Programming
Value