Drive
TYPE
(Inverter)
CIMR-P7U"
Capacity
(kVA)
40P4
1.4
40P7
1.6
41P5
2.8
42P2
4.0
43P7
5.8
44P0
6.6
45P5
9.5
47P5
13
4011
21
4015
26
4018
30
4022
38
4030
51
4037
59
4045
73
4055
95
4075
120
4090
140
4110
180
4132
200
4160
230
4185
315
4220
390
4300
510
Table 1.4 400V Class Heat Loss Data
Rated
Cooling
Output
Fin Side
Current
(W)
(A)
1.8
14
2.1
17
3.7
36
5.3
59
7.6
80
8.7
90
12.5
127
17
193
27
232
34
296
40
389
50.4
420
67.2
691
77
801
96
901
125
1204
156
1285
180
1614
240
1889
260
2388
304
2636
414
2791
515
3797
675
5838
Physical Installation 1 - 12
Total
Internal
Watt
Unit Side
Loss
(W)
(W)
39
53
41
58
48
84
56
115
68
140
70
160
81
209
114
307
158
390
169
465
201
590
233
653
297
989
332
1133
386
1287
478
1682
562
1847
673
2287
847
2736
1005
3393
1144
3936
1328
3964
1712
5509
2482
8319
Cooling
Method
Self
Self
Self
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan
Fan