Over Torque Detection; Under Torque Detection - YASKAWA P7 User Manual

Table of Contents

Advertisement

After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by
the output current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least
the Torque Detection Time (L6-03), then the Torque Detection Function will change the state of any digital output configured
for Torque Detection (H2-01/H2-02= "B: Trq Det 1 N.O.", or "17: Trq Det 1 N.C.").
L6-02
L6-02
L6-02
L6-03
* When the output current drops below the Torque Detection Level by
approximately 10% of the Drive's rated output current the digital output is reset.
Fig. 38 Over Torque Detection
L6-03
* When the output current rises above the Torque Detection Level by
approximately 10% of the Drive's rated output current the digital output is reset.
Fig. 39 Under Torque Detection
*
L6-03
CLOSED
Torque detection level 10%
*
L6-03
Programming 5 - 47
Torque detection level -10%
*
t
Closed
Open
TIME
*
t
Closed
Open
t
TIME

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents