2 Parameter Description

2.17 Main Menu - FC Closed Loop - Group 20

2.17.1 Drive Closed Loop, 20-**
2
This parameter group is used for configuring the closed loop PID Controller, that controls the output frequency of the frequency converter.
2.17.2 Feedback, 20-0*
This parameter group is used to configure the feedback signal for the frequency converter's closed loop PID Controller. Whether the frequency converter
is in Closed Loop Mode or Open Loop Mode, the feedback signals can be shown on the frequency converter's display. It can also be used to control a
frequency converter analog output, and be transmitted over various serial communication protocols.
20-00 Feedback 1 Source
Option:
[0]
No function
[1]
Analog input 53
[2] *
Analog input 54
[3]
Pulse input 29
[4]
Pulse input 33
[7]
Analog input X30/11
[8]
Analog input X30/12
[9]
Analog Input X42/1
[10]
Analog Input X42/3
[11]
Analog Input X42/5
[100]
Bus feedback 1
[101]
Bus feedback 2
[102]
Bus feedback 3
160
Function:
Up to three different feedback signals can be used to provide the feedback signal for the frequency
converter's PID Controller.
This parameter defines which input will be used as the source of the first feedback signal.
Analog input X30/11 and Analog input X30/12 refer to inputs on the optional General Purpose I/O
board.
®
MG.20.O4.02 - VLT
is a registered Danfoss trademark
®
VLT
AQUA Drive Programming Guide