2.12 Main Menu - Smart Logic - Group 13

2.12.1 13-** Prog. Features Prog. Features
Smart Logic Control (SLC) is essentially a sequence of user defined actions (see par.13-52
associated user defined
event
(see par.13-51
together in pairs. This means that when
be evaluated and if evaluated TRUE,
FALSE, nothing happens (in the SLC) during the current scan interval and no other
event
event
evaluates
[0] (and only
event
[1]. It is possible to programme from 1 to 20
When the last
event
/
action
has been executed, the sequence starts over again from
event / actions:
Starting and stopping the SLC:
Starting and stopping the SLC can be done by selecting
event
evaluates
[0]). The SLC starts when the Start Event (defined in par.13-01
SL Controller Mode
par.13-00
). The SLC stops when the
starts programming from scratch.
2.12.2 13-0* SLCLC-0# LC Settings
Use the SLC settings to activate, deactivate and reset the Smart Logic Control.
13-00 SL Controller Mode
Option:
[0] *
Off
[1]
On
13-01 Start Event
Option:
[0] *
False
[1]
True
[2]
Running
SL Controller Event
[x]) is evaluated as TRUE by the SLC. Events and
event
[0] is fulfilled (attains the value TRUE),
action
[1] will be executed and so on. Only one
event
[0]) each scan interval. Only when
events
and
actions
.
On
Off
[1] or
[0] in par.13-00
Stop Event
(par.13-02
Function:
Disables the Smart Logic Controller.
Enables the Smart Logic Controller.
Function:
Select the boolean (TRUE or FALSE) input to activate Smart Logic Control.
Enters the fixed value of FALSE in the logic rule.
Enters the fixed value TRUE in the logic rule.
See parameter group 5-3* for further description.
®
MG.20.O4.02 - VLT
is a registered Danfoss trademark
SL Controller Action
actions
action
[0] is executed. After this, the conditions of
event
will be evaluated at any time. If an
events
will be evaluated. This means that when the SLC starts, it
[0] is evaluated TRUE, will the SLC execute
event
[0] /
action
[0]. The illustration shows an example with three
SL Controller Mode
. The SLC always starts in state 0 (where it
Start Event
) is evaluated as TRUE (provided that
Stop Event
Reset SLC
) is TRUE. par.13-03
2 Parameter Description
[x]) executed by the SLC when the
are each numbered and linked
event
[1] will
event
is evaluated as
action
[0] and start evaluating
On
[1] is selected in
resets all SLC parameters and
2
119