2 Parameter Description
2.16 Main Menu - Data Readouts 2 - Group 18
2.16.1 18-0* Maintenance LogLG-0# Maintenance Log
2
This group contains the last 10 Preventive Maintenance logs. Maintenance Log 0 is the latest log and Maintenance Log 9 the oldest.
By selecting one of the logs and pressing OK, the Maintenance Item, Action and time of the occurrence can be found in par.18-00
Item
Maintenance Log: Date and Time
– par.18-03
The Alarm log button on the LCP allows access to both Alarm log and Maintenance log.
18-00 Maintenance Log: Item
Array [10]
Range:
0 N/A*
[0 - 255 N/A]
18-01 Maintenance Log: Action
Array [10]
Range:
0 N/A*
[0 - 255 N/A]
18-02 Maintenance Log: Time
Array [10]
Range:
0 s*
[0 - 2147483647 s]
18-03 Maintenance Log: Date and Time
Array [10]
Range:
0 N/A*
[0 - 0 N/A]
NB!
When mounting an Analog I/O MCB 109 option card, a battery back-up of date and time is included.
158
.
Function:
Locate the meaning of the Maintenance Item in the description of par.23-10
Function:
Locate the meaning of the Maintenance Item in the description of par.23-11
Function:
Shows when the logged event occurred. Time is measured in seconds since last power-up.
Function:
Shows when the logged event occurred.
NB!
This requires that the date and time is programmed in par. 0-70
Time
.
Date format depends on the setting in par. 0-71
Time Format
the setting in par.0-72
NB!
The frequency converter has no back up of the clock function and the set date/
time will reset to default (2000-01-01 00:00) after a power down unless a Real
Time Clock module with back up is installed. In par.0-79
to program for a Warning in case clock has not been set properly, e.g. after a
power down. Incorrect setting of the clock will affect the time stamps for the
Maintenance Events.
®
MG.20.O4.02 - VLT
is a registered Danfoss trademark
®
VLT
AQUA Drive Programming Guide
Date Format
, while the time format depends on
.
Maintenance Log:
Maintenance Item
.
Maintenance Action
Date and
Clock Fault
it is possible