Illustration 2.6: Legend: FC=frequency converter; f
=frequency out; P
=P system; P
=P setpoint
O
S
SL
1) Systems where the integrated PI controller is used for controlling pressure or temperature e.g. boost systems with a pressure feed back signal applied
Configuration Mode
to the frequency converter from a pressure transducer. Par. 1-00,
, must be set for Closed Loop and the PI Controller configured for
desired reference and feed back signals.
Example: Boost system.
If no flow is detected, the frequency converter will increase the set point for pressure to ensure a slight over pressure in the system (boost to be set in
par. 22-45,
Setpoint Boost
).
The feedback from the pressure transducer is monitored and when this pressure has dropped with a set percentage below the normal set point for
pressure (Pset), the motor will ramp up again and pressure will be controlled for reaching the set value (Pset).