Fieldbus interface:
In parameter p2040 you define the time for cyclic data exchange for process data.
Setting range 0 - 2000 s.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F01910) is issued by the Modbus if p2040 is set to a value > 0 ms and no
process data is requested within this time period.
COMM BOARD:
In parameter p8840 you define the time for cyclic process data exchange.
Setting range 0 - 2000 s.
The time depends on the amount of data to be transferred and the control.
"Setpoint timeout" (F08501) is issued by the Modbus if p8840 is set to a value > 0 ms and no
process data is requested within this time period.
A.1.4.8
Messages and parameters
Faults and alarms
Note
You can find the description of faults and alarms in the converter List Manual.
Fault number
F01910
A01925
F08501
A08526
A08555
Overview of important parameters
Note
For a description of the parameters, see the converter List Manual.
Parameter
p0978[0...n]
p2030
p2040
r2050[0...19]
188
Message
Fieldbus: Setpoint timeout
Modbus TCP connection interrupted
PN/COMM BOARD: Setpoint timeout
PN/COMM BOARD: No cyclic connection
Modbus TCP commissioning fault
Description
List of drive objects
Fieldbus interface protocol selection
Fieldbus interface monitoring time:
CO: IF1 PROFIdrive PZD receive word
Configuration Manual, 08/2017, A5E36912609A