Siemens SINAMICS Configuration Manual page 44

Industrial security, medium-voltage converter
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

Security measures for SINAMICS
5.2 Write protection and know-how protection
5. The end user copies the "User" directory to the new memory card and inserts it into the
new Control Unit.
6. The end user switches on the drive.
When powering up, the Control Unit checks the new serial numbers and deletes the values
p7759 and p7769 if they match.
After it has powered-up without any errors, the Control Unit is ready for operation. The know-
how protection is active.
If the serial numbers do not match, then fault F13100 is output.
If required, the end user must re-enter the changed parameters from the OEM exception
lists.
Calling the "Load to File System" dialog box
1. Call STARTER.
2. Open the required project.
3. Select the required drive unit in the project navigator of your STARTER project.
4. Call the "Load to file system" function.
The "Load to File System" dialog box opens.
Figure 5-7
44
Load to file system (default setting)
Configuration Manual, 08/2017, A5E36912609A
Industrial Security