Installation and Commissioning

Setting parameters of measuring points

Once the levels have been set on the device and teleprotection signaling is functioning properly,
alarm operating thresholds can now be set for monitoring the PU3f and CLE outputs.
These can be set in the menu <Adjustment> <Measuring points>.
Figure 33:
Table 43:
Standard
Read
-6dB of current value
Entering "0" in the Min field deactivates monitoring. It is recommended that if the system is operat-
ing properly the current level values should be accepted with <Read> and the alarm thresholds de-
fined with <-6dB of current value>.
Failure to attain the PU3f output level activates the display on the PU3f module (flashing red LED
of the used interface) and transmitter alarm (SAL) on the CLE module.
Failure to attain the CLE output level activates the display SAL.
Page - 42
Setting the alarm thresholds.
Setting options for measuring points
Menu option
Edition p3_3_2x 08/09
SWT 3000 Equipment Manual
Comments
Default values stored in the program are imported
for the individual measuring points
The current measured values are read from the
measuring points in the SWT 3000 device
The current measured values are halved and en-
tered in the Min field as the threshold value for the
measuring point alarm.