Logic Input Connections
It is not necessary to connect to the logic inputs unless you require the enhanced functionality they provide.
The two contact closures inputs are pre-configured to provide the following functionality:
Contact Closure 1 = Tare
Contact Closure 2 = Net/Gross Toggle
When the Tare contact is closed the display will show zero and the display mode will be
switched to Net.
The logic input provides a 5 Vdc signal. When connected to this common, a current of 1mA will flow. Because this
is a small signal only switches with gold contacts or self-cleaning contacts are recommended.