Introduction / Overview The T24-RM1 offers dual power relays capable of mains power switching. These relays can be configured as high, low or window alarms and can be associated with a group of up to 8 T24 acquisition modules per relay.
A change in error state of a module specified in a relays list of inputs The T24-RM1 also features a third Alarm relay. The Alarm relay is energised from start up, (connection made between COM and NO). The relay de-energises if an error is detected, an error is classed as a timeout and optionally can include Integrity error or low Battery.
If you have a USB version of the base station (T24-BSu) then you just need to plug this into a USB socket on your PC. If you are using an alternative base station then please refer to the appropriate manual. Mantracourt Electronics Limited T24-RM1 User Manual...
T24 Toolkit The T24 Toolkit provides a means of simple configuration of the T24-RM1 and associated acquisition module along with useful tools to aid integration. Calibration of the acquisition modules is also provided. Run the T24 Toolkit software application. General Pages Setup Base Station Communications Select USB as the interface and select 1 as the Base Station Address.
• Click the Pair button on the toolkit. • You now have 10 seconds to re-apply power to the T24-RM1 module. • If you connect successfully the toolkit will change to the Information page. If the pairing fails try again.
The above charts show the traffic from a Wi-Fi network and it can be seen to be operating over channels 6 to 9 and it would be best (though not essential) to avoid using these channels. Mantracourt Electronics Limited T24-RM1 User Manual...
Information This page shows you information about the connected device. Items you can change: Name You can enter a short descriptive name (11 characters) which may help you recognise this device in the future. Mantracourt Electronics Limited T24-RM1 User Manual...
Encryption Key Only devices with identical encryption keys can communicate. You can isolate groups of devices on the same channel or just use the key to ensure the data cannot be read by somebody else. Mantracourt Electronics Limited T24-RM1 User Manual...
All configuration information including calibration data will be overwritten. The file extension is tcf. Advanced Settings Click this button to enter the Advanced Settings Page. Here are settings which do not normally require changing. Mantracourt Electronics Limited T24-RM1 User Manual...
Enter up to eight Data Tags the data from which will be used to determine the value compared to the set point to control relay 2. Zero Offset [1-2] This value will be subtracted from the total of the summed data from the data tags for Relay 1. Mantracourt Electronics Limited T24-RM1 User Manual...
This value set on offset between when the relay is engergised and de- energised creating a de-bounce for the relay. (See diagram on next page) Latching [1-2] Latching locks the state of the relay when it passes the set point. Mantracourt Electronics Limited T24-RM1 User Manual...
Page 15
Operation and Hysteresis Settings _________ RELAY ENERGISED OPTIONAL LATCH ------------- RELAY DE-ENERGISED Hysteresis Set Point Hysteresis OPTIONAL LATCH Normal Operation Inverted Operation Mantracourt Electronics Limited T24-RM1 User Manual...
The acquisition modules should have a Sleep Delay set so that after the relay module has been powered down the acquisition modules then return to sleep. Enter zero to disable this feature. Mantracourt Electronics Limited T24-RM1 User Manual...
Digital inputs 1 and 2 are used. Items you can change: Timeout Enter a time in seconds that if exceeded the T24-RM1 will affect the relay state according to the error action, as well as set the alarm relay and light the time out LED Error Action For each relay the action upon error detection can be defined as ;...
RAD24i; a small increase or reduction in antenna elevation will often improve reception. Range underwater is only a decimetre or so depending on packet rate. Best performance underwater is obtained by using low packet rates and immersing water-proofed antennae rather than water-tight enclosures containing the antennae. Mantracourt Electronics Limited T24-RM1 User Manual...
Operational Current All Relays Active 155** Operational Temperature Range Deg C Storage Temperature Range Deg C Power Relays 240V 5A Alarm Relay 1A 24V DC 120 V AC ** At 12 Volt nominal Supply Mantracourt Electronics Limited T24-RM1 User Manual...
(2) this device must accept any interference received, including interference that may cause undesired operation. CAUTION: If the device is changed or modified without permission from Mantracourt Electronics Ltd, the user may void his or her authority to operate the equipment.
Section 15.247 (emissions). Acquisition modules have been certified by the FCC for use with other products without any further certification (as per FCC section 2.1091). Changes or modifications not expressly approved by Mantracourt could void the user’s authority to operate the equipment.
Page 22
The CE marking must have a height of at least 5mm except where this is not possible on account of the nature of the apparatus. The CE marking must be affixed visibly, legibly, and indelibly. Mantracourt Electronics Limited T24-RM1 User Manual...
Radio and Telecommunications Terminal Equipment Directive 1999/5/EC, FCC CFR Title 47 part 15c BS EN 61000-4-2 and BS EN 61000-4-3 following the provisions of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC. December 2007 Brett James FCC ID:VHARAD24 Development Manager Mantracourt Electronics Limited. Mantracourt Electronics Limited T24-RM1 User Manual...
Any corrective maintenance required after the warranty period should be performed by 'Mantracourt' approved personnel only. ISO 9001 REGISTERED FIRM In the interests of continued product development, Mantracourt Electronics Limited reserves the right to alter product specifications without prior notice. DESIGNED & MANUFACTURED IN THE UK Code No. 517-920 Issue 1.3 08.10.13...