Figure 34:

Diagnostics view

Table 8:
Meaning of the diagnostics
information
Note
The graphical user interface
5.8
Diagnostics view
Once you have completed your project and connected to your MELSEC-WS safety
controller, you can perform a diagnostics on your system. In the Diagnostics view, a
complete history of all messages, information, warnings and error messages of a
connected MELSEC-WS safety controller is available in the upper part of the window.
If you click on one of the entries in the list, details on the selected message are
displayed in the lower part of the window.
Keyword
Code
Hexadecimal error code
Description
Error description
Time stamp
Total CPU module operation time at the time of error (days:hours:min:sec)
Local time
Time when error occurred (PC system time).
This value is not displayed for historical errors.
Cycle power
Total number of times the CPU module has been switched on
Type
Error type (e.g. information, warning, recoverable error, critical error)
Source
Module that detected the error
Category
Part of the module that detected the error
Information
Internal information about the error
Occurrence
Number of times this error has occurred.
counter
If an error occurs several times in a row, only the last occurrence will be
recorded and the occurrence counter is increased.
Power on hour
Total time since the last power-on of the CPU module. This value is reset at
every restart.
Operating hours
Total power-on time of the CPU module
Block
Diagnostics memory area in the CPU module.
8 = RAM (volatile, error occurred within the current power-on cycle)
88 = EEPROM (non-volatile, error occured in a previous power-on cycle)
Register
Index in the diagnostics memory area
CPU channel
Internal hardware channel (A or B) of the module that detected the error
For a list of the most important error codes, possible causes and potential rectification
measures please see the Safety Controller User's Manual.