Chapter 9
205
Logic programming – Function blocks
The Enable output changes to High, if ...
all Release inputs are High and stay High, and
each activated Operator input has changed to Low at least once (this may occur at
different times as well) after the MELSEC-WS safety controller has changed from
the Stop state to the Run state or after a rising or a falling edge (depending on the
configuration) has been detected at the Cycle request input, and
all activated Operator inputs have changed to High subsequently.
The Enable output changes to Low, if ...
one or more of the Release inputs is Low, or
one or more of the Operator inputs is Low, or
a rising or a falling edge (depending on the configuration) has been detected at the
Cycle request input.
Sequence/timing diagram
Figure 195:
Sequence/timing diagram for the Multi operator function block