The graphical user interface
Note
The configuration of any connected SICK EFI-compatible devices is not included in
the exported partial application. Therefore these devices have to be reconfigured.
How to exchange a safety I/O module in a project:
 Load the project with the safety I/O module you want to exchange.
 Add the desired new safety I/O module to the hardware configuration.
 Move the connected elements from the old module to the new module. This way the
logic connections will be preserved.
 Delete the old module.
 This method does not work for elements that are used in combination with a Fast
Note
shut off function block, because these elements can not be moved to another
module anymore.
 This method does not work either for grouped elements like e.g. operating mode
selector switches and switches with interlock.
Chapter 5
46