Mitsubishi Electric WS0-CPU0 Operating Manual page 90

Melsec ws series, safety controller setting and monitoring tool
Table of Contents

Advertisement

Chapter 7
Figure 56:
CPU outputs in the output
selection window
Note
Figure 57:
Flexi Link routing logic
example
Recommendation
87
Flexi Link
Configuring the Flexi Link routing for Station A
 In the Logic editor for Station A, add an additional Routing N:N function block,
configure it for two inputs and outputs and connect its inputs to the WS0-XTIO
inputs for the reset button and the emergency stop button.
 Drag two outputs of the Station A CPU module on the logic editor worksheet. You
will find the outputs in the output selection window under CPU1 or CPU3.
 A square with the letter A-D within it denotes a bit within the Flexi Link process
image.
 Each output can be used only once. Used outputs are displayed green.
 Connect the outputs of the Routing N:N function block to the two CPU1[A] outputs
(e.g. Info 0.3.CPU1[A].EFI1 and Info 0.4.CPU1[A].EFI1) as shown in Figure 57.
 Note which input is being routed to which output.
In more complex projects, configure the routing connections on a separate page in the
logic editor. Otherwise the logic design could get confusing.