User Mode Switch - Mitsubishi Electric WS0-CPU0 Operating Manual

Melsec ws series, safety controller setting and monitoring tool
Table of Contents

Advertisement

Chapter 9
Figure 150:
Function block diagram for
the User mode switch
function block
Table 71:
Parameters of the User
mode switch function block
167
Logic programming – Function blocks
9.8.9

User mode switch

Function block diagram
General description
The User mode switch function block selects an output depending on an input value.
Output x is High if Input x is High.
The function block supports 2 to 8 inputs and the corresponding outputs.
Only one input may be High at any time (1 out of n). If no input or more than one input
is High, the output that was High last is kept High for the configured discrepancy time.
After expiration of the discrepancy time, the Fault present output changes to High
and all outputs change to the value defined in the error output combination.
If in the first logic cycle after the transition from the Stop state to the Run state there is
no valid input combination, the configured error output combination is applied to the
outputs and the Fault present output changes to High immediately.
Parameters of the function block
Parameter
Discrepancy time
Error output combination
Number of inputs or Number of outputs
Use fault present
Possible values
0 to 10 seconds in steps of 10 ms
Checked outputs will be High and not checked
outputs will be Low when Fault present is High.
2 to 8
 With
 Without