Chapter 9
Table 92:
Parameters of the muting
function blocks
209
Logic programming – Function blocks
When an override input is configured, test pulse outputs may not be used for the
configuration of the safety inputs.
Separate lines have to be used for the sensor signals A1 and A2 (B1 and B2).
A line that is independent of other input signals has to be used for the signals for
Reset and Reset required in order to exclude unintentional resetting of the system.
The line must furthermore be laid protected.
The total muting time cannot be set to indefinite (inactive) without additional
precautions being taken. If the total muting time is set to indefinite, additional
measures have to be taken to ensure that no one can access the hazardous area
while muting is activated.
9.10.2
Parameters of the function blocks
The following table lists the possible configuration parameters of the muting function
blocks.
Parameter
Direction detection
Sequence monitoring
Condition of other sensor
pair for muting start
Muting end condition
Muting total time
Add. muting time when
ESPE is clear
Sensor signal gap
monitoring
Concurrency monitoring
time
C1 input
Conveyor input
Override input
Min. override pulse time
Possible values
Disabled
Only with Parallel muting and Sequential muting:
Forward (A1/A2 first)
Backward (B1/B2 first)
Not selectable. Defined by selection of the muting function block:
Enabled: With Sequential muting
Disabled: With Parallel muting or Cross muting
Both inputs are clear
Only with Parallel muting and Sequential muting:
If last muting sensor is active
With muting sensor pair
With ESPE
0 = disabled, 5 s to 3600 s, resolution 1 s
0 ms, 200 ms, 500 ms, 1000 ms
0 = disabled, 10 to 1000 ms, resolution 10 ms. If enabled, the
value has to be greater than the logic execution time.
0 = disabled, 10 to 3000 ms, resolution 10 ms. If enabled, the
value has to be greater than the logic execution time.
With
Without
With
Without
With
Without
100 ms
350 ms