Goodrive300-16 special inverter for HVAC
Function
code
PID1 reference
PID1 feedback
P09.10
source 1
P09.16
Output feature
P09.17
Proportional gain
P09.18
Integral time
P09.19
Differential time
P22.00
HVAC function
P22.01
Hibernation type
Hibernation starting
P22.02
frequency
Hibernation starting
P22.03
deviation
Hibernation entry
P22.04
delay time
PID1 reference
P22.05
P22.06
Max. boost time
Set
Name
value
1.00
0.10
0.00
40.00Hz
5.0%
60.0s
10.0%
boost
10.000s
situations
Adjustable according to the actual
1
situations
Adjustable according to the actual
0
situations
Adjustable according to the actual
situations
Adjustable according to the actual
situations
Adjustable according to the actual
situations
1
HVAC function enabled
Hibernate according to the running
1
frequency
Allow hibernation only when the running
frequency is smaller than the value and
the hold time is larger than P22.04.
Relative to the maximum PID1 value
Allow hibernation only when the output
feature is positive, feedback is larger than
reference, the absolute value of the actual
deviation is larger than the value and the
hold time is larger than P22.04.
Allow hibernation only when the output
feature is negative, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.04.
Relative to PID1 reference
Used to avoid the case where the inverter