Goodrive300-16 special inverter for HVAC
Code
Fault
Parameters
DNE
downloading
fault
Grounding
ETH1
shortcircuit
fault 1
Grounding
ETH2
shortcircuit
fault 2
Speed
dEv
deviation fault
Maladjustment The control parameters of
STo
Cause
and affected by strong
interference.
Communication fault.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is mistake on the data
storage of the keypad.
The output of the inverter is
short circuited with the
ground.
There is fault in the current
detection circuit.
The actual motor power
sharply differs from the
inverter power.
The output of the inverter is
short circuited with the
ground.
There is fault in the current
detection circuit.
The actual motor power
sharply differs from the
inverter power.
The load is too heavy or
stalled.
36
Commissioning guidelines
Solution
Change the hardware and ask
for service.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask
for service.
Repack-up the data in the
keypad.
Check if the connection of the
motor is normal or not
Change the hoare
Change the main control panel
Set motor parameters correctly.
Check if the connection of the
motor is normal or not
Change the Hoare
Change the main control panel
Set motor parameters correctly.
Check the load and ensure it is
normal. Increase the detection
time.
Check whether the control
parameters are normal.
Check the load and ensure it is
Need help?
Do you have a question about the Goodrive 300-16 and is the answer not in the manual?