Goodrive300-16 special inverter for HVAC
Code
Fault
EEPROM
EEP
operation fault
Braking unit
bCE
fault
Running time
END
arrival
Electrical
OL3
overload
Keypad
PCE
communication
fault
Parameters
UPE
uploading
fault
Cause
The offset between the
parameters from autotune
and the standard parameter
is huge
Autotune overtime
Error of controlling the write
and read of the parameters
Damage to EEPROM
Braking circuit fault or
damage to the braking pipes
The external braking resistor
is not sufficient
The actual running time of
the inverter is above the
internal setting running time.
The inverter will report
overload pre-alarm
according to the set value.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
and affected by strong
interference.
There is circuit fault on the
communication of the
keypad and main board.
The connection of the
keypad wires is not good or
broken.
The keypad wire is too long
35
Commissioning guidelines
Solution
reidentify
Check the motor connection and
set the parameter.
Check if the upper limit
frequency is above 2/3 of the
rated frequency.
Press STOP/RST to reset
Change the main control panel
Check the braking unit and ,
change new braking pipe
Increase the braking resistor
Ask for the supplier and adjust
the setting running time.
Check the load and the overload
pre-alarm point.
Check the keypad wires and
ensure whether there is mistake.
Check the environment and
avoid the interference source.
Change the hardware and ask
for service.
Check the keypad wires and
ensure whether there is mistake.
Change the hardware and ask
for service.