Goodrive300-16 special inverter for HVAC
Function
code
Hibernation waking
P22.07
frequency
Hibernation waking
P22.08
deviation
Hibernation waking
P22.09
delay time
Variable frequency
P22.10
motor operation
P22.11
A motor type
P22.12
B motor type
P22.13
C motor type
Pressure allowance
P22.19
when adding motor
Set
Name
value
20.00Hz
2.0%
2.0s
4.0%
runs continuously when the running
frequency reaches the upper limit while
the feedback cannot reach the set value
after boost, the inverter will enter
hibernation immediately after boost time.
PID output directly starts superposition
from the frequency when waking up in
close loop.
Relative to the maximum PID1 value
Allow waking up only when the output
feature is positive, feedback is smaller
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.09.
Allow waking up only when the output
feature is negative, feedback is larger
than reference, the absolute value of the
actual deviation is larger than the value
and the hold time is larger than P22.09.
Min. hibernation time
Set to the fixed variable frequency motor,
invalid when A~H motors are set to
0
variable frequency motor, set to power
frequency motors when using multiple
motors
2
Power frequency motor
2
Power frequency motor
2
Power frequency motor
Adjustable according to the actual
situations
18
Commissioning guidelines
Remark