Goodrive300-16 special inverter for HVAC
Function
Name
code
Automatic
P11.06
current limit
Frequency-
decreasing
P11.07
ratio during
current limit
Overload
pre-alarm
P11.08
of motor/
inverter
Detailed instruction of parameters
50.0~200.0%
0.00~50.00Hz/s
0x000~0x131
LED ones:
0: Overload pre-alarm of the motor, relative to the
rated current of the motor
1: Overload pre-alarm of the inverter, relative to the
rated current of the inverter
LED tens:
0: The inverter continues to work after underload
pre-alarm
1: The inverter continues to work after underload
pre-alarm and the inverter stops to run after
overload fault
2: The inverter continues to work after overload
pre-alarm and the inverter stops to run after
underload fault
3. The inverter stops running after overload and
unerload fault
LED hundreds :
0: Detection all the time
1: Detection in constant running
94
Appendix A
Default
Modify
value
◎
160.0%
3.00
◎
Hz/s
○
0x000