Goodrive300-16 special inverter for HVAC
Function
Name
code
month and
day when fire
enabled
Current time
P21.04
when fire
enabled
P22 Group HVAC special function
HVAC
P22.00
function
Hibernation
P22.01
type
Hibernation
P22.02
starting
frequency
Hibernation
P22.03
starting
deviation
Hibernation
P22.04
entry delay
time
PID1
P22.05
reference
boost value
P22.06
Max. boost 0.000~60.000s
Detailed instruction of parameters
00.00~23.59
0: Invalid
1: Valid
0: Limited frequency running
1: Hibernation according to running frequency
2: Hibernation according to deviation
P00.05~P00.04 (upper limit frequency)
Allow hibernation when the running frequency is
smaller than the value and the hold time is larger
than P22.04.
0.0~30.0% (relative to Max. PID1 value)
when the output feature is positive, the feedback is
larger than reference, the actual deviation is larger
than the value and the hold time is larger than
P22.04. Allow hibernation when the output feature
is negative, the feedback is smaller than reference,
the actual deviation is larger than the value and the
hold time is larger than P22.04.
0.0~3600.0s
-100.0~100.0% (relative to PID1 reference)
117
Appendix A
Default
Modify
value
●
00.00
◎
0
○
1
○
40.00Hz
○
5.0%
○
60.0s
○
10.0%
○
10.000s