Goodrive300-16 special inverter for HVAC
Function
Name
code
Max. output
P00.03
frequency
Upper limit
P00.04
of running
frequency
Lower limit
P00.05
of running
frequency
A
P00.06
frequency
command
B
P00.07
frequency
command
B
frequency
P00.08
command
reference
Combination
P00.09
of setting
source
Detailed instruction of parameters
3:Reserved
Note: 1, 2 and 3 are extension functions which
need corresponding extension cards.
Max. (P00.04, 10.00)~400.00Hz
P00.05~P00.03 (Max. output frequency)
0.00Hz~P00.04 (Upper limit of running frequency)
0: Keypad
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDI setting
5: Simple PLC program setting
6: Multi-step speed running setting
7: PID1 control setting
8: MODBUS communication setting
9: Profibus/CANopen/BACnet/Devicenet
communication setting
10: Ethernet communication setting
11: Reserved
0: Maximum output frequency
1: A frequency command
0: A
1: B
2: A+B
3: A-B
4: Max (A, B)
5: Min (A, B)
40
Appendix A
Default
Modify
value
◎
50.00Hz
◎
50.00Hz
◎
0.00Hz
○
0
○
2
○
0
○
0