Goodrive300-16 special inverter for HVAC
Voltage
degree
Lot number
2.4 Rated specifications
Model
GD300-16-004G/5R5P-4
GD300-16-5R5G/7R5P-4
GD300-16-7R5G/011P-4
GD300-16-011G/015P-4
GD300-16-015G/018P-4
GD300-16-018G/022P-4
GD300-16-022G/030P-4
GD300-16-030G/037P-4
GD300-16-037G/045P-4
GD300-16-045G/055P-4
GD300-16-055G/075P-4
GD300-16-075G/090P-4
GD300-16-090G/110P-4
GD300-16-110G/132P-4
GD300-16-132G/160P-4
Note:
1. The input current of inverters 4~132kW is detected when the input voltage is 380V and
there is no DC reactors and input/output reactors.
2. The rated output current is defined when the output voltage is 380V.
3. The output current can not exceed the rated output current and the output power can not
exceed the rated output power in the voltage range.
③
Voltage degree
④
IP degree
⑤
Market lot number
Rated output
power(kW)
4/5.5
5.5/7.5
7.5/11
11/15
15/18.5
18.5/22
22/30
30/37
37/45
45/55
55/75
75/90
90/110
110/132
132/160
S2: AC 1PH 220V(-15%)~240V(+10%)
2: AC 3PH 220V(-15%)~240V(+10%)
4: AC 3PH 380V(-15%)~440V(+10%)
6: AC 3PH 520V(-15%)~690V(+10%)
Protective degree (the protective degree
of standard products can be default)
0-IP00;
1-IP20;
2-IP21;
5-IP54;
6-IP65;
HVAC: heating, ventilation and air
conditioning, can be omitted
Rated input
current(A)
13.5/19.5
19.5/25
25/32
32/40
40/47
47/56
56/70
70/80
80/94
94/128
128/160
160/190
190/225
225/265
265/310
10
Product overview
Rated output
current(A)
9.5/14
14/18.5
18.5/25
25/32
32/38
38/45
45/60
60/75
75/92
92/115
115/150
150/180
180/215
215/260
260/305
Need help?
Do you have a question about the Goodrive 300-16 and is the answer not in the manual?