INVT Goodrive 300-16 Operation Manual page 44

For hvac
Table of Contents

Advertisement

Goodrive300-16 special inverter for HVAC
Function
Name
code
between
FWD/REV
rotation
Stopping
P01.15
speed
Detection
P01.16
of stopping
speed
Detection
time of
P01.17
feedback
speed
Terminal
running
protection
P01.18
when
powering
on
Action if
running
frequency<
P01.19
lower limit
frequency
(valid >0)
Restart
P01.21
after power
off
The waiting
P01.22
time of
restart after
Detailed instruction of parameters
1:Switch after the starting frequency
0.00~100.00Hz
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid
for vector control)
0.00~100.00s (only valid when P01.16=1)
0: The terminal running command is invalid when
powering on
1: The terminal running command is valid when
powering on
0: Run at the lower-limit frequency
1: Stop
0: Disable
1: Enable
0.0~3600.0s (valid when P01.21=1)
43
Appendix A
Default
Modify
value
0.50Hz
0
0.50s
0
0
0
1.0s

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Goodrive 300-16 and is the answer not in the manual?

This manual is also suitable for:

Gd300-16Goodrive300-16

Table of Contents