Goodrive300-16 special inverter for HVAC
Function
Name
code
between
FWD/REV
rotation
Stopping
P01.15
speed
Detection
P01.16
of stopping
speed
Detection
time of
P01.17
feedback
speed
Terminal
running
protection
P01.18
when
powering
on
Action if
running
frequency<
P01.19
lower limit
frequency
(valid >0)
Restart
P01.21
after power
off
The waiting
P01.22
time of
restart after
Detailed instruction of parameters
1:Switch after the starting frequency
0.00~100.00Hz
0: Detect according to speed setting (no stopping
delay)
1: Detect according to speed feedback (only valid
for vector control)
0.00~100.00s (only valid when P01.16=1)
0: The terminal running command is invalid when
powering on
1: The terminal running command is valid when
powering on
0: Run at the lower-limit frequency
1: Stop
0: Disable
1: Enable
0.0~3600.0s (valid when P01.21=1)
43
Appendix A
Default
Modify
value
◎
0.50Hz
◎
0
◎
0.50s
○
0
◎
0
○
0
○
1.0s
Need help?