Goodrive300-16 special inverter for HVAC
Function
Name
code
when
inverter
stops
Second
when
P20.08
inverter
stops
P20.09
Clock fault
Current
P20.10
second
P21 Group
Fire override function
P21.00
Fire mode
Running
P21.01
frequency
in fire mode
Fire mode
P21.02
flag bit
P21.03
Current
Detailed instruction of parameters
00~59s
0: Disabled
1: Enabled
00~59s
0: Invalid
1: Fire mode 1
2: Fire mode 2
P21.00=0, the fire mode is invalid. The inverter
runs in normal mode and stops at fault. When
P21.00 is non-zero and the fire signal is enabled,
the fire mode will be valid. The inverter will run in
the frequency P21.01.
Fire mode 1, the inverter will keep running unless it
is damaged;
Fire mode 2, the inverter will keep running except
OUT1, OUT2, OUT3, OC1, OC2, OC3, OV1, OV2,
OV3 and SPO faults
0.00Hz~P00.03 (Max. output frequency)
0~1
After the inverter runs in fire mode for 5 minutes,
set the flag bit without warranty handling.
01.01~12.31
116
Appendix A
Default
Modify
value
○
00s
○
0
●
00s
◎
0
○
50.00Hz
●
0
●
00.00