Goodrive300-16 special inverter for HVAC
Function
Name
code
time
Hibernation
P22.07
waking
frequency
Hibernation
P22.08
waking
deviation
Hibernation
P22.09
waking
delay time
Variable
frequency
P22.10
motor
selection
P22.11
A motor
Detailed instruction of parameters
Used to avoid the case where the inverter runs
continuously when the running frequency reaches
the upper limit while the feedback cannot reach the
set value after boost, the inverter will enter
hibernation immediately after boost time.
P00.05~P0.03 (upper limit frequency)
PID output directly starts superposition from the
frequency when waking up in close loop.
0.0~30.0% (relative to Max. PID1)
Allow waking up only when the output feature is
positive, feedback is smaller than reference, the
absolute value of the actual deviation is larger than
the value and the hold time is larger than P22.09.
Allow waking up only when the output feature is
negative, feedback is larger than reference, the
absolute value of the actual deviation is larger than
the value and the hold time is larger than P22.09.
0.0~3600.0s
Minimum hibernation time
0: Fixed variable frequency motor
1: Circulation variable frequency motor
P22.10=0, invalid when A~H are set to variable
frequency motors; the corresponding motors can
be only set to power frequency motors when using
multiple motors. Goodrive300-16 can form the
system of 1 fixed variable frequency motor +8
power frequency motors.
P22.10=1, at least two motors of A~H need to be
set to variable frequency motors. Goodrive300-16
can form the system of 4 or 3 variable frequency
motors +2 power frequency motors.
0: Invalid
118
Appendix A
Default
Modify
value
○
20.00Hz
○
2.0%
○
2.0s
◎
0
◎
0