Goodrive300-16 special inverter for HVAC
Code
Fault
communication
fault
BACnet
E-DP
communication
fault
Devicenet
E-CAN
communication
fault
Low PID1
feedback
HP
pre-alarm
Inverter
non-stop fault
High PID1
feedback
LP
pre-alarm
Inverter
non-stop fault
Cause
Corresponding resistor is not
dialed
The communication baud
rate is uneven
The ambient interference is
too strong.
The Ethernet communication
is not selected to right.
The ambient interference is
too strong.
The connection is not sound
The communication baud
rate is uneven
The ambient interference is
too strong.
PID1 feedback value
continues P22.45 and is
smaller than P22.44
PID1 feedback value
continues P22.47 and is
larger than P22.46
38
Commissioning guidelines
Solution
Draw out the correspond resistor
Set the same baud rate
Check the environment and
avoid the interference.
Check the communication
method selection.
Check the environment and
avoid the interference.
Check the connection
Set the same baud rate
Check the environment and
avoid the interference.
Check PID1 actual feedback
value is normal
Check PID1 feedback detection
device has no fault
Check PID1 actual feedback
value is normal
Check PID1 feedback detection
device has no fault