2. INSTALLATION
2.1.4.
Vibrations
The controller can support vibrations from 10 to 55 Hz,
20 m/s
, in all directions (X, Y and Z).
2
If the device is mounted on a support that exceeds these
limits, it is advisable to provide a suspension system to re-
duce vibrations.
2.1.5.

Minimum space for ventilation

The temperature in the housing containing the controller
must NEVER exceed 55°C. NEVER block the ventilation slits.
Advice. The lower the temperature in which the de-
vice works, the longer the life of its electronic com-
ponents.
Attention! Forced cooling (for example, with a fan)
of the rear of the controller may cause measure-
ment errors.
2.1.6.
Positioning
The controller must be positioned so that the display is not
subject to direct sunlight or to very strong sources of light.
If necessary, filter direct light, for example, with a reflective
screen.
The controller must be tilted between 30° and 120°, as
shown in the figure.
Controllers not in scale
Figure 7 - Positioning the controller
2.1.7.
Fastening to the panel
1.
Insert the die-cut rubber gasket between the controller
and the panel. The gasket (supplied) is indispensable for
ensuring the declared protection index of the faceplate.
2.
Insert the device into the hole previously made on the
panel.
3.
Place the supplied bracket(s) onto the rear of the con-
troller.
4.
Tighten the screws to fasten the device to the panel.
The tightening torque must be between 0,3 and 0,4 N m.
20
The following figures show how to fasten the three control-
ler models.
120 °
30 °
Figure 8 - Fastening the 650
Figure 9 - Fastening the 1250
Figure 10 - Fastening the 1350
80208G_MHW_650-1250-1350_01-2017_ENG