4. CONFIGURATION

4.24.1. STP.xx - Value of step xx

Acronym
STP.xx
CUSTOM LINEARIZATION STEP
The parameter shows and sets the value of the various steps, with xx from 0 to 32.
The start scale value goes in STP.00 and the full-scale value in STP.32.
The value of the nth step corresponds to the input: mV start scale + n*ΔmV con ΔmV = (mV full scale - mV start scale)/32.
Unit of measurement:
Options:
-1999...9999
4.24.2. MV.STA - Setting mV at start of scale
Acronym
MV.STA
MV START SCALE
The parameter shows and sets the value in millivolts at start of scale if the input is a thermocouple.
Unit of measurement:
Options:
-19.99...99.99
4.24.3. MV.FUL - Setting mV at full scale
Acronym
MV.FUL
MV FULL SCALE
The parameter shows and sets the value in millivolts at full scale if the input is a thermocouple.
Unit of measurement:
Options:
MV.STA + 1...99.99
4.24.4. MV.50C - Setting mV at temperature of 50 °C
Acronym
MV.50C
MV AT 50 'C
The parameter shows and sets the value in millivolts at 50°C if the input is a thermocouple.
Unit of measurement:
Options:
-1.999...9.999
130
Scrolling message
Scale points
Scrolling message
mV
Scrolling message
mV
Scrolling message
mV
Submenu
LINRZ
Submenu
LINRZ
Submenu
LINRZ
Submenu
LINRZ
80208G_MHW_650-1250-1350_01-2017_ENG
Attributes
R W
Attributes
R W
Attributes
R W
Attributes
R W