ASSEMBL Y AND INSTALLATION

Assembly of Integrated Controller and Operator Panel

UL requirements

- Installation category (overvoltage category) II.
- A device suitable for use in environments with pollution
degree 2.
- Maximum temperature of the air around the device 50°C
(UL 508).
- Use on a flat surface with protection type 1.

Hole dimensions

For correct installation, observe the dimensions of the
templates shown in the illustration.
The dotted line shows the maximum size of the front panel.
Attention: the panel on which the Integrated Controller and
93
GF VEDO SL 35CT
Protection against infiltrations of
water
The Integrated Controller and Operator Panel offers, first of
all, a degree of protection of IP65. It is therefore possible to
install the device in particularly dusty environments or areas
subject to splashes of water without problems:
the compartment in which the device is housed also has
to be dust and waterproof;
the panel on which the device is installed must be per-
fectly smooth and flat on the front;
the hole in the panel must scrupulously respect the di-
mensions indicated;
the device has to be fastened tightly to the panel, to
allow the gasket fitted at the back to ensure water tight-
ness.

Vibrations

The Integrated Controller and Operator Panel can support
vibrations up to 150 Hz:
from 5 to 9 Hz: sinusoidal 3.5 mm constant;
from 9 to 150 Hz: sinusoidal with acceleration equal to
1 G.
Should the device be mounted on a support that exceeds
12
187.5
GF VEDO SL V70CT
Figure 4 - Panel hole dimensions for GF_VEDO SL
Operator Panel is mounted has to have the following cha-
racteristics:
be sufficiently stiff and strong so that it does not bend
during use;
be between 1 and 12 mm thick, to allow the fastening of
the device with the terminals supplied;
if the use of the USB transfer cable is envisaged, read
the notes on its installation first.
these limits it is necessary to envisage a system for the su-
spension and mitigation of the vibrations.

Minimum spaces for ventilation

The temperature of the compartment that houses the Inte-
grated Controller and Operator Panel must not exceed
50 °C. Figure 3 – Free spaces for ventilation shows the mini-
mum free distances recommended in the installation of the
device in a closed compartment.

Positioning

The Integrated Controller and Operator Panel has to be posi-
tioned in order to guarantee the following conditions:
the screen must not be directly lit by the sun or particu-
larly bright light sources.
If necessary, screen direct rays, using an antiglare shut-
ter for example;
there must be no sudden temperature changes;
there must be a low explosion risk: it can be connected
to elements that operate in environments with a hazar-
dous atmosphere (flammable or explosive) only through
appropriate and suitable types of interface, compliant to
the safety standards in force;
low presence of magnetic fields