gefran 650 Installation And Instruction Manual page 43

Pid temperature controllers
Hide thumbs Also See for 650:
Table of Contents

Advertisement

3.4.3.
Setting up the PID
0000
Home page
0000
Press > 2 seconds
0
Enter password (default = 1) with the
PASS1
Press 5 times (if the model does not have remote setpoint input and current
transformer options and is not the Programmer)
PID
Submenu
PID
S.TUNE
SOFT.S
A.TUNE
Cntr
0000
Home page
0000
The PID submenu also lets you:
set the Soft-Start time (parameter SOFT.T, default =
0.0);
select the type of Auto-Tuning used (parameter Aut.t,
default = CONTI);
set the derivative time (parameter DERV.S, default = 1);
set the proportional heating band or hysteresis in ON-
OFF control (parameter H.PB, default = 1.0);
set the integral heating time (parameter H.IT, default =
4.00);
set the derivative heating time (parameter H.DT, defau-
lt = 1.00);
set the maximum heating power limit (parameter
H.P.HI, default = 100.0);
set the minimum heating power limit (parameter
H.P.LO, default = 0.0);
select the cooling fluid (parameter COOL, default =
FAN);
set the cooling setpoint compared to the heating
setpoint (parameter C.SP, default = 0.0);
set the proportional cooling band or hysteresis in ON-
OFF control (parameter C.PB, default = 1.0);
set the integral cooling time (parameter C.IT = 4.00);
set the derivative cooling time (parameter C.DT = 1.00);
set the maximum cooling power limit (parameter
C.P.HI, default = 100.0);
41
and
Enable or disable Self-Tuning (default = OFF) with the
Description of parameter and list of options on page 85
Enable or disable Soft-Start (default = OFF) with the
Description of parameter and list of options on page 85
Enable or disable Auto-Tuning (default = OFF) with the
Description of parameter and list of options on page 85
Select the control (default = H.PID) with the
Description of parameter and list of options on page 86
Press > 2 seconds
keys
and
and
keys
set the minimum cooling power limit (parameter
C.P.LO, default = 0.0);
set the Manual Reset value (parameter RESET, default
= 0);
set the Reset Power value (parameter P.RST, default =
0.0);
set the Antireset value (parameter A.RST, default = 0);
set the Feedforward Power value (parameter, default =
0.0);
set the deadband (parameter DEAD.B, default = 0);
set the fault action power (parameter FAULT, default =
0.0);
set the setpoint gradient in raise (parameter GRAD.I,
default = 0.0);
set the setpoint gradient in lower (parameter GRAD.D,
default = 0.0);
select the gradient unit of measurement (parameter
Unit, default = DIG/S);
set the control output gradient (parameter GRAD.O,
dafault = 0.0);
80208G_MHW_650-1250-1350_01-2017_ENG
3. COMMISSIONING
and
keys
keys
and
keys

Hide quick links:

Advertisement

Table of Contents
loading