4.13.28. Unit - Unit of measurement of gradient

Acronym
Unit
GRADIENT UNIT OF MEASURE
The parameter shows and sets the unit of measurement of gradient GRAD.I and GRAD.D.
The parameter appears only if GRAD.I or GRAD.D are greater than "0.0".
Unit of measurement:
Options:
DIG/S
DIG/M = Digit/minute
4.13.29. GRAD.O - Gradient of control output
Acronym
GRAD.O
CONTROL OUTPUT GRADIENT
The parameter shows and sets the gradient used by the control output.
The gradient is used to limit rapid changes in the control output.
If the parameter is "0.0" the gradient is disabled.
Unit of measurement:
Options:
0.0...100.0
4.13.30. LBA.TM - Tripping delay
Acronym
LBA.TM
WAITING TIME FOR LBA ALARM TRIP
The parameter shows and sets the delay time for tripping of the LBA alarm.
If the parameter is "0.0" the LBA alarm is disabled.
When the LBA alarm is active, it is automatically cancelled if the PV rises (in heating) or lowers (in cooling), or by setting
the parameter AL.ACK = On on the user configuration menu or by switching to Manual mode.
Unit of measurement:
Options:
0.0...500.0
4.13.31. LBA.PW - Power delivered when LBA alarm trips
Acronym
LBA.PW
POWER LIMITS BY LBA ALARM CONDITION
The parameter shows and sets the power value delivered when the LBA alarm trips.
Unit of measurement:
Options:
-100.0...100.0
80208G_MHW_650-1250-1350_01-2017_ENG
Scrolling message
-
= Digit/second
Scrolling message
% / second
Scrolling message
Minutes
Scrolling message
%
4. CONFIGURATION
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
Submenu
Attributes
PID
R W
91