5.1.
Inputs
5.1.1.
Analog input
Available only for GRM-H-x-x-x-AN-x-x-x-x-x-x model
Settings
5.1.1.1. Analog input type
Acronym
App / GF_eXpress menu
tyP
The parameter sets the type of analog input.
Options:
0 Input disabled
1 0...10V
2 0...5V
3 0...20mA
4 4...20mA
5 Potentiometer
6 Potentiometer with custom calibration (*)
(*) full scale calibration only, activated by key
5.1.1.2. Analog input scale minimum limit
Acronym
App / GF_eXpress menu
Lo.S
Inputs Analog input
The parameter sets the analog input scale minimum limit. It can be used to recalibrate the analog
input or set a minimum power. Example, if Lo.S=10.0, when the 0..10V input is at 0V, the delivered
power will be 10.0%, at 10V it will be 100.0%. Intermediate values will be heated.
min...max: -100.0...+200.0
5.1.1.3. Analog input scale maximum limit
Acronym
App / GF_eXpress menu
HI.S
Inputs Analog input
The parameter sets the analog input scale maximum limit. It can be used to recalibrate the analog
input or set an upper power limit. Example, if HI.S=90.0, when the 0..10V input is at 10V, the power
delivered will be 90.0%, at 0V it will be 0.0%. The intermediate values will be heated.
min...max: Lo.S...+200.0
5.
PARAMETER DESCRIPTIONS
Inputs Analog input
819XX_MAN_GRM-H_11-2022_ENG_pag. 27
Attribute Retentive
Description
R/W
■
Attribute Retentive
Description
R/W
■
Attribute Retentive
Description
R/W
■
U.M.
Default
1
U.M.
Default
s.p.
0.0
U.M.
Default
s.p.
100.0