Parameter Descriptions; Inputs; Analog Input; Analog Input Type - gefran GRM-H 15 Configuration And Programming Manual

Compact power controllers, analog command and io-link communication
Table of Contents

Advertisement

5.1.

Inputs

5.1.1.

Analog input

Available only for GRM-H-x-x-x-AN-x-x-x-x-x-x model
Settings

5.1.1.1. Analog input type

Acronym
App / GF_eXpress menu
tyP
The parameter sets the type of analog input.
Options:
0 Input disabled
1 0...10V
2 0...5V
3 0...20mA
4 4...20mA
5 Potentiometer
6 Potentiometer with custom calibration (*)
(*) full scale calibration only, activated by key

5.1.1.2. Analog input scale minimum limit

Acronym
App / GF_eXpress menu
Lo.S
Inputs  Analog input
The parameter sets the analog input scale minimum limit. It can be used to recalibrate the analog
input or set a minimum power. Example, if Lo.S=10.0, when the 0..10V input is at 0V, the delivered
power will be 10.0%, at 10V it will be 100.0%. Intermediate values will be heated.
min...max: -100.0...+200.0

5.1.1.3. Analog input scale maximum limit

Acronym
App / GF_eXpress menu
HI.S
Inputs  Analog input
The parameter sets the analog input scale maximum limit. It can be used to recalibrate the analog
input or set an upper power limit. Example, if HI.S=90.0, when the 0..10V input is at 10V, the power
delivered will be 90.0%, at 0V it will be 0.0%. The intermediate values will be heated.
min...max: Lo.S...+200.0
5.

PARAMETER DESCRIPTIONS

Inputs  Analog input
819XX_MAN_GRM-H_11-2022_ENG_pag. 27
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
Attribute Retentive
Description
R/W
U.M.
Default
1
U.M.
Default
s.p.
0.0
U.M.
Default
s.p.
100.0